EasyManua.ls Logo

Rockwell Automation Allen-Bradley LiquiFlo 2.0 - AC Line I;O Board Description (Frame 3 Only)

Rockwell Automation Allen-Bradley LiquiFlo 2.0
268 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication D2-3518-4 - January 2020 25
About the Drive Chapter 2
AC Line I/O Board
Description (Frame 3 Only)
The following signals are available at the AC Line I/O board terminal block. The
AC Line I/O board is labeled as item 21 in Figure 4
. See Figure 9 for terminal
identification.
Digital Inputs
The AC Line I/O board terminal block provides terminals for four digital inputs
(terminals 22...26). These digital inputs cannot be configured.
Digital Outputs
The AC Line I/O board terminal provides terminals for six digital outputs that
are non user-configurable terminals 5...16 and 27...32. The state of these six
outputs can be changed by writing to inverter parameter Appl Digital Out (30).
Digital output 1 is always connected to the shunt trip circuit; do not use digital
output 1 for anything else.
The digital output devices are form C relays capable of switching 250V AC at 8 A
or 30V DC at 8 A.
Analog Inputs
The AC Line I/O board contains no component hardware for user-configurable
analog inputs.
Analog Outputs
The AC Line I/O board terminal block provdes terminals for two special
purpose analog outputs, using terminals 1-2 and 17-18. These outputs are not
user-configurable.

Table of Contents