148 Rockwell Automation Publication D2-3518-4 - January 2020
Chapter 9 Parameter Descriptions
Table 9 - Speed Select Inputs
Assigns an input function to the user-configurable digital inputs of the drive. 
Note that digital inputs Run, Jog, Clear-Faults, and Direction control functions 
are operational only when the mask parameters are set for these functions.
See AC Line I/O Board Description (Frame 3 Only)
 on page 25 through 
Combined I/O Board Description (Frame 4 Only)
 on page 29 for a description 
of I/O hardware that is present on this drive and is controlled by the inverter.
Table 10 - Default Values for Parameters 361...366
The input functions are:
1 = Enable: If the input is closed, the drive can run (start permissive). If the input 
is open, the drive will not start.
If the drive is already running when this input is opened, the drive coasts and 
indicates not enabled on the OIM (if present). This is not considered a fault 
condition, and no fault is generated.
If multiple enable inputs are configured, the drive will not run if any of them are 
open.
2 = Clear Faults: This function allows an external device to reset drive faults 
through the terminal block if clearing faults from the terminal block is enabled 
using the Logic Mask (276) and Fault Clr Mask (283). An open-to-closed 
transition on this input resets the current fault (if any).
Speed Select Inputs
321 Reference Source
000 Speed Ref A Sel
0 0 1 Speed Ref B Sel
0 1 0 Preset Speed 2
0 1 1 Preset Speed 3
1 0 0 Preset Speed 4
1 0 1 Preset Speed 5
1 1 0 Preset Speed 6
1 1 1 Preset Speed 7
Parameter No. Default Value
361 0 = Unused
362 0 = Unused
363 0 = Unused
364 0 = Unused
365 0 = Unused
366 0 = Unused