70 Rockwell Automation Publication D2-3518-4 - January 2020
Chapter 9 Parameter Descriptions
Inverter Parameters
The output frequency present at T1, T2, and T3 (U, V, and W).
The value of the active frequency command.
The total RMS output current present at T1, T2, and T3 (U, V, and W).
The amount of output current that is in phase with the fundamental voltage 
component.
The amount of output current that is out of phase with the fundamental voltage 
component.
1
Output Freq
Range: +/-400.0 Hz   [0.1 Hz]
Default: Read Only
Access: 0 Path: Monitor > Metering
See also:
2 
Commanded Freq
Range: +/- 400.0 Hz   [0.1 Hz]
Default: Read Only
Access: 0 Path: Monitor > Metering
See also:  
3 
Output Current
Range: 0.0...3276.7 A   [0.1 A]
Default: Read Only
Access: 0 Path: Monitor > Metering
See also:  
4 
Torque Current
Range: +/- 1800.0 A   [0.1 A]
Default: Read Only
Access: 1 Path: Monitor > Metering
See also:  
5 
Flux Current
Range: +/- 1800.0 A   [0.1 A]
Default: Read Only
Access: 1 Path: Monitor > Metering
See also:  
6 
Output Voltage
Range: 0.0...600.0V AC   [0.1V AC]
Default: Read Only
Access: 1 Path: Monitor > Metering
See also: