Rockwell Automation Publication D2-3518-4 - January 2020 225
Troubleshooting the Drive Chapter 10
Figure 89 - OIM Version Screens at the Product and Component Levels
Device Items
The Device Items selection provides access to a list of diagnostic parameters. 
These parameters should be adjusted by qualified personnel only. See Figure 90
.
Figure 90 - Accessing the Device Item Information
Checking the Power 
Modules with Input Power 
Off
Use the following procedure to check the Power Module circuitry of the drive 
with power off.
1. Turn off and lock out input power. Wait 5 minutes.
2. Verify that there is no voltage at the input power terminals of the drive.
3. Check the DC bus potential with a voltmeter to make sure that the DC 
bus capacitors are discharged.
ATTENTION: The parameters in the Device Items menu must be set by a 
qualified person who understands the significance of setting them accurately. 
Failure to observe this precaution could result in bodily injury.
Diag: Prodct Ver
Date: mm/dd/yyyy
FW Ver:         x.xxx
Series:  X
Cmp
F1
F1
Diag: OIM Comp
Prev
LCD OIM Standard
Control Board
Prdt
Next
Flash
To Component
Level
To Product
Level
F1 F3
Flash F/W
Information
Diag: Comp Ver
FW Ver:     x.xxx
HW Ver:     xxx
S#:       xxxxxxxx
Diagnostics
:
Device Items
Fault Info
Monitor Lang
P0: LiquiFlo 2.0
    Stopped      Auto
Main Menu
Diagnostics
Status Infor
Highlight Diagnostics icon
Highlight item
Dev  Item #
Param name
Param value
Dflt
Scroll through
items
F1
Display default
>>
ATTENTION:  DC bus capacitors retain hazardous voltages after input power has 
been disconnected. After disconnecting input power, wait 5 minutes for the DC 
bus capacitors to discharge and then check the voltage with a voltmeter to 
ensure the DC bus capacitors are discharged before touching any internal 
components. Failure to observe this precaution could result in severe bodily 
injury or loss of life.