Rockwell Automation Publication D2-3518-4 - January 2020 147
Parameter Descriptions Chapter 9
361
362
363
364
365
366
Digital In1 Sel
Digital In2 Sel
Digital In3 Sel
Digital In4 Sel
Digital In5 Sel
Digital In6 Sel
Range: 0 = Not Used
1 = Enable
2 = Clear Faults
(1)
3 = Aux Fault
4 = Stop - CF
(2)
5 = Start
6 = Fwd/Reverse
2
7 = Run
(3)
8 = Run Forward
3
9 = Run Reverse
3
10 = Jog
11 = Jog Forward
12 = Jog Reverse
13 = Stop Mode B
14 = Bus Reg Md B
15 = Speed Sel 1
(4)
16 = Speed Sel 2
4
17 = Speed Sel 3
4
18 = Auto/Manual
19 = Local
20 = Acc2 & Dec2
21 = Accel 2
22 = Decel 2
23 = MOP Inc
24 = MOP Dec
25 = Excl Link
26 = PI Enable
27 = PI Hold
28 = PI Reset
29 = Pwr Loss Lvl
30 = Precharge En
(1) When Digital In”x” Sel is set to option 2 (Clear Faults), the stop key cannot be used to clear a fault condition.
(2) Typical 3-Wire Inputs. These require that only 3-wire functions are chosen. Including 2-wire selections causes a type 2 alarm.
(3) Typical 2-Wire Inputs. These require that only 2-wire functions are chosen. Including 3-wire selections causes a type 2 alarm.
(4) To access Preset Speed 1, set Speed Ref A Sel to Preset Speed 1. See Tab le 9
.
Default: See Table 1 0
Access: 361...366 = 0 Path: Inputs & Outputs > Digital Inputs
See also: 96, 100, 124, 140, 156, 162, 194, 380