Rockwell Automation Publication D2-3518-4 - January 2020 163
Parameter Descriptions Chapter 9
The rectifier rated RMS input voltage is displayed as x.x V AC.
The rectifier rated RMS input current is displayed as x.x A.
The rectifier software version number is displayed as x.xxx.
The allowed level of imbalance in input voltage entered as x.x%.
An Input V Imbalance fault (fault 226) is generated if Line V Imbalance (23) is
greater than V Imbalance Lmt (60) for this amount of time.
27
Rated Volts
Range 0.0...6553.5 V AC [0.1V AC]
Default: Read Only
Access: 0 Path: Monitor > Drive Data
See also:
28
Rated Amps
Range: 0.0...6553.5 A [0.1 A]
Default: Read Only
Access: 0 Path: Monitor > Drive Data
See also:
29
Control SW Ver
Range: x.xxx
Default: Read Only
Access: 0 Path: Monitor > Drive Data
See also:
60
V Imbalance Lmt
Range: Path: 0.0 to 20.0% [0.1%]
Default: 10.0
Access: 0 Path: Configuration > AC Line
See also: 23, 61
61
V Imbalance Time
Range: 1.0...10.0 seconds [0.1 seconds]
Default: 1.0
Access: 0 Path: Configuration > AC Line
See also: 23, 60