210 Rockwell Automation Publication D2-3518-4 - January 2020
Chapter 10 Troubleshooting the Drive
SW OverCurrent 36 The drive output current has exceeded the software current
limit.
Check for excess load, improper DC boost setting. DC brake volts set too
high.
UnderVoltage 4
DC bus voltage fell below the minimum value of: 305V DC
input.
Enable/disable with inverter Fault Config 1(238).
Monitor the incoming AC line for low voltage or power interruption.
UserSet1 Chksum 101 The checksum read from the user set does not match the
checksum calculated.
These faults can be cleared by writing a nonzero value to
inverter Save To User Set (199).
Re-save user set using inverter Save To User Set (199).
UserSet2 Chksum 102
UserSet3 Chksum 103
Table 22 - Fault Descriptions and Corrective Actions (Frame 4) (Continued)
Fault
No.
Type
Description Action
Table 23 - Fault Names Cross-Referenced by Fault Number
No.
(1)
Fault No.
(1)
Fault No.
(1)
Fault
2 Auxiliary Input 48 Params Defaulted 214 Reactor Temp
3 Power Loss 63 Shear Pin 215 Rctfr HW Unused
(3)
4 UnderVoltage 64 Drive Overload 216 Rctfr Gnd Fault
5 OverVoltage 70 HW Fault 217 Rctfr Base Temp
7 Motor Overload 71...76 Port 1...6 Adapter 218 Rctfr IGBT Temp
8 Invtr Base Temp 77 IR Volts Range 219 Rctfr IT Overld
9 Invtr IGBT Temp 78 FluxAmpsRef Rang 220 Rctfr I2T Overld
12 HW OverCurrent 79 Excessive Load 221 Ride Thru Abort
13 Ground Fault 80 AutoTune Aborted 222 High AC Line
14 Inv Shunt Trip 81...86 Port 1...6 DPI Loss 223 Low DC Bus
15 Hi Vdc Shunt 87 IXo VoltageRange 224 Rctfr Over Volt
18 Invtr I Offset U 100 Parameter Chksum 225 Input I Imbalance
19 Invtr I Offset V 101 UserSet1 Chksum 226 Input V Imbalance
20 Invtr I Offset W 102 UserSet2 Chksum 227 AC Line Lost
21 Rctfr I Offset R 103 UserSet3 Chksum 228 Line Feq Lost
22 Rctfr I Offset S 104 Pwr Brd Chksum1 229 Rctfr Checksum
23 Rctfr I Offset T 105 Pwr Brd Chksum2 230 Invtr HW Unk
24 Decel Inhibit 106 Incompat MCB-PB 231 Rctfr HW Unk
25 OverSpeed Limit 107 Replaced MCB-PB 232 Rctfr Not OK
29 Analog In Loss 120 I/O Mismatch
(3)
233 Precharge Closed
30 NTC Demux Fail
(2)
121 I/O Comm Loss 234 Precharge Opened
31 Inv Temp Switch
(2)
122 I/O Board Fail 3 235 Rctfr Pwr Board
33 Auto Rstrt Tries 123 Invtr Unk IO Brd
(2)
236 Rctfr IO Board
35 Current Fbk Lost 197...199 Invtr Dsat U-, V-, W-
(2)
237 Not At Voltage
36 SW OverCurrent 200...202 Invtr Dsat U, V, W
(3)
238 Rctfr Not Login
37 Motor I Imbalance 200...202 Invtr Dsat U+, V+, W+
(2)
239 Power Phased ACB
38 Phase U to Grnd 203...205 Invtr Over Cur U, V, W 240 Rctfr Gate Kill
(2)
39 Phase V to Grnd 206 Invtr HW Unused
(3)
241...243 Rctfr Dsat R-, S-, T-
(2)