EasyManua.ls Logo

Rockwell Automation Allen-Bradley LiquiFlo 2.0 - Page 36

Rockwell Automation Allen-Bradley LiquiFlo 2.0
268 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
36 Rockwell Automation Publication D2-3518-4 - January 2020
Chapter 3 Planning the Installation
Table 4 - Environmental Conditions
Determining Total Area Required Based on Drive Dimensions
Overall drive dimensions are identified in these figures:
Frame 3 drives 180264-A03 and 180264-A06 in Figure 14
Frame 4 drives 180580-A07 and 180580-A09 in Figure 16
Overall power module dimensions are identified in these figures:
Frame 3 power modules LF200460AAR and LF200608CCR in Figure 15
Frame 4 power modules LF200900CCRand LF201215CCR in Figure 17
Condition Specification
Operating Temperature
(inside NEMA/UL Type 1 enclosure)
0...+55 °C
(1)
(32...131 °F)
(1) With typical heat rise inside a cabinet, 40 °C (104 °F) ambient outside usually results in 55 °C (131 °F) inside.
Ambient Temperature
(outside NEMA/UL Type 1 enclosure)
0...+40 °C (32...104 °F)
Storage Temperature (Ambient) - 40...65 °C (- 40...149 °F)
Humidity 5%...95% (non-condensing)

Table of Contents

Related product manuals