48 Rockwell Automation Publication D2-3518-4 - January 2020
Chapter 4 Mounting The Power Module and Grounding the Drive
Use the following procedure to lift and mount the LiquiFlo 2.0 power module:
1. Use an overhead or portable hoist (minimum 2 ton rated capacity) to
attach a free-fall chain to the chain secured to the power module. Take up
any vertical slack in the chain.
2. Use the hoist to carefully lift the power module from the horizontal
shipping pallet.
3. Position the power module in the prepared mounting location.
4. Machine fasten the power module enclosure using 1/2-inch bolts, grade 5
or better, with compression washers. Recommended tightening torque is
11.3...13.5 N•m (100...120 lb•in).
ATTENTION: Do not use input and output busbars for lifting or handling.
Otherwise, damage to equipment may result.
ATTENTION: Mechanically support conductors to minimize mechanical load on
input and output busbars. Otherwise, damage to equipment may result.