Provides a manual or automatic method for setting IR Voltage Drop (62) and 
Flux Current Ref (63), which affect sensorless vector performance. Valid only 
when Torque Perf Mode (53) is set to Sensrls Vect or SV Economize.
Ready (0) = Parameter returns to this setting following a Static Tune or Rotate 
Tune. It also permits manually setting IR Voltage Drop (62) and Flux Current 
Ref (63).
Static Tune (1) = A temporary command that initiates a non-rotational motor 
stator resistance test for the best possible automatic setting of IR Voltage Drop. A 
start command is required following the initiation of this setting. The parameter 
returns to Ready (0) following the test, at which time another start transition is 
required to operate the drive in normal mode. Used when the motor cannot be 
uncoupled from the load.
Rotate Tune (2) = A temporary command that initiates a Static Tune followed 
by a rotational test for the best possible automatic setting of Flux Current Ref. A 
start command is required following initiation of this setting. 
The parameter returns to Ready (0) following the test, at which time another 
start transition is required to operate the drive in normal mode. 
Calculate (3) = This setting uses motor nameplate data to automatically set IR 
Voltage Drop and Flux Current Ref.
61 
Autotune
Range: 0 = Ready
1 = Static Tune
2 = Rotate Tune
3 = Calculate
 
Default: 3 = Calculate
Access: 0 Path: Motor Control > Torq Attributes
See also: 53, 62, 63
ATTENTION: Rotation of the motor in an undesired direction can occur during 
this procedure (Autotune [61] = Rotate Tune [2]). To guard against possible 
injury and/or equipment damage, it is recommended that the motor be 
disconnected from the load before proceeding.
IMPORTANT Rotate Tune (2) is used when motor is uncoupled from the load. Results may 
not be valid if a load is coupled to the motor during this procedure.
62 
IR Voltage Drop
Range: 0.0 to Motor NP Volts x 0.25   [0.1V AC]
Default: Based on Drive Rating
Access: 1  Path: Motor Control > Torq Attributes
See also: 53