Rockwell Automation Publication 750-RM004A-EN-P - April 2018 47
Selection Considerations Chapter 1
Frame 14 PowerFlex 755TR drive
PowerFlex 755TL drives not available in ratings this high (frame 11…12)
All other non-regenerative applications PowerFlex 755TL drive
Table 15 - Suggested Migration Solution (Continued)
Table 16 - 400V AC Input Electrical Rating Cross Reference
PowerFlex 700S (20D…) PowerFlex 755TL/TR (20G1G/F…)
Frame
Size
Catalog
Number
ND O/P
kW
ND O/P
Amps
HD O/P
kW
HD O/P
Amps
Frame
Size
755TL Low
Harmonic
Catalog
Number
(1)
755TR Regen / Low
Harmonic
Catalog Number
(1)
ND O/P
kW
ND O/P
Amps
HD O/P
kW
HD O/P
Amps
F9 20DC261...
20DC300...
132
160
261
300
110
132
205
245
F8 20G1GnC302… 20G1FnC302… 160 302 132 260
F10 20DC385... 200 385 160 300 F8 20G1GnC367… 20G1FnC367… 200 367 160 302
F10 20DC460... 250 460 — — F8 20G1GnC460… 20G1FnC460… 250 460 200 367
F10 20DC460...
20DC500...
—
250
—
500
200
250
385
420
F8 20G1GnC540… 20G1FnC540… 315 540 250 460
F8 20G1GnC585… 20G1FnC585… 315 585 250 472
F11 20DC590...
20DC650...
315
355
590
650
250
—
520
—
F8 20G1GnC650… 20G1FnC650… 355 650 315 540
F8 20G1GnC750… 20G1FnC750… 400 750 315 585
F11 20DC650...
20DC730…
—
400
—
730
315
355
590
650
F8 20G1GnC770… 20G1FnC770… 400 770 355 650
F12 20DC820...
20DC920...
450
500
820
920
400
—
730
—
F9 20G1GnC920… 20G1FnC920… 500 920 400 770
F12 20DC920...
20DC1K0...
—
560
—
1030
450
500
820
920
F9 20G1GnC1K0… 20G1FnC1K0… 560 1040 500 920
F13 20DC1K1... — — 560 1030 F9 20G1GnC1K1… 20G1FnC1K1… 630 1112 500 1040
F13 20DC1K1... 630 1150 — — F9 20G1GnC1K2… 20G1FnC1K2… 710 1175 560 1090
F13 20DC1K3...
20DC1K4...
710
800
1300
1450
630
—
1150
—
F9 20G1GnC1K4… 20G1FnC1K4… 800 1465 630 1175
F13 20DC1K4... — — 710 1200 F10 20G1GnC1K6… 20G1FnC1K6… 850 1590 710 1465
F10 20G1GnC1K7… 20G1FnC1K7… 1000 1715 800 1480
F10 20G1GnC2K1… 20G1FnC2K1… 1250 2156 1000 1715
F11 — 20G1FnC2K8… 1650 2849 1400 2330
F12 — 20G1FnC3K5… 2000 3542 1650 3032
(1) <n> In catalog number is enclosure type; catalog code 3= IP21, catalog code 4= IP54.