EasyManua.ls Logo

Rockwell Automation Allen-Bradley PowerFlex 700S - Task Time; Test Points; Thermal Regulator

Rockwell Automation Allen-Bradley PowerFlex 700S
218 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
192 Rockwell Automation Publication PFLEX-RM003E-EN-E - January 2011
Chapter 1 Detailed Drive Operation
Parameters 793 [Xsync In 3]…795 [Xsync Out 3 Dly] can be used to
synchronize a floating point parameter and delay it one scan.
Parameter 787 [Xsync Gen Period] sets the scan time of the synch
generator. The following options are available:
The default setting is 1 = “1 ms.
Task Time
Task times are adjustable for the 3 tasks in the drive.
Task 1 includes the Speed Regulator, Speed/Position Feedback, Torque
Control, Current Control, Analog I/O and Digital I/O
Task 2 includes the Speed Reference Control, Position Control and
Process PI Control
Task 3 includes User Functions
The times are set by parameter 146 [FW TaskTime Sel] as listed below:
After changing the task time in parameter 146 [FW TaskTime Sel] a drive reset
must be performed (via the HIM navigate from the Main Menu to Diagnostics >
Faults > Reset Device) or drive power must be cycled before the change will be
active. Parameter 148 [FW TaskTime Actl] will then display the actual task time.
Test Points
Test points are used to monitor values in the drive for diagnostic information.
[xxxx TP Sel] selects a value to monitor for diagnostics.
[xxxx TP Data] shows the value selected by [xxxx TP Sel].
Thermal Regulator
Refer to Drive Overload on page 45.
0 = 0.5 ms
1 = 1 msec
2 = 2 msec
3 = 4 msec
4 = 8 msec
Parameter 146 Task 1 Time Task 2 Time Task 3 Time
0 0.5 ms 2 ms 8 ms
1 0.5 ms 1 ms 8 ms
2 0.25 ms 1 ms 8 ms

Table of Contents

Other manuals for Rockwell Automation Allen-Bradley PowerFlex 700S

Related product manuals