EasyManua.ls Logo

Rockwell Automation Allen-Bradley PowerFlex 700S - Datalinks

Rockwell Automation Allen-Bradley PowerFlex 700S
218 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication PFLEX-RM003E-EN-E - January 2011 29
Detailed Drive Operation Chapter 1
Datalinks:
In the ControlLogix system, Datalinks are transmitted as DInt. In order to send
or receive Real (floating-point) parameters a COP (copy) instruction must be
utilized. The copy instruction in ControlLogix performs a bitwise copy. Set the
length of the copy instruction to a value appropriate for the destination data type.
Example to write a floating point Datalink:
Parameter 125 [Torque Pos Limit] sets the positive torque limit for the motor.
[Torque Pos Limit] is a Real (floating point) parameter scaled in per unit (a value
of 1.000 is equivalent to 100% motor torque). This example will write [Torque
Pos Limit] with a Datalink.
1. Link parameter 125 [Torque Pos Limit] to parameter 651 [DPI Data In
A1].
2. Set parameter 650 [DPI In DataType] bit 0 “DPI A1 Real” = 1.
3. Verify that the Datalink is enabled in the 20-COMM module.
4. In RSLogix5000, create a tag “PF700S_P125_TorquePosLimit” of type
“REAL.
5. Use the COP instruction to copy the tag
“PF700S_P125_TorquePosLimit” to the DINT output tag for Datalink
A1 (PF700S:O.UserDefinedData(0) in this example).
6. A value of 1.000 in the tag “PF700S_P125_TorquePosLimit” will write a
value of 1.000 to parameter 125 in the drive.
Example to read a floating point Datalink:
Parameter 303 [Motor Torque Ref ] displays the torque output to the motor.
Parameter 303 is a Real (floating point) parameter scaled in per unit (a value of
1.000 is equivalent to 100% motor torque).
1. Link parameter 660 [DPI Data Out A1] to parameter 303 [Motor Torque
Ref].
2. Set parameter 659 [DPI Out DataType] bit 0 “DPI A1 Real” = 1.
3. Verify that the Datalink is enabled in the 20-COMM module.
4. In RSLogix5000, create a tag “PF700S_P303_MotorTorqueRef ” of type
“REAL.
5. Use the COP instruction to copy the DINT input tag for Datalink A1
(PF700S:I.UserDefinedData(0) in this example) to the tag
“PF700S_P303_MotorTorqueRef.

Table of Contents

Other manuals for Rockwell Automation Allen-Bradley PowerFlex 700S

Related product manuals