5-10 MD60 AC Drive User Manual
5.8 Output Disconnect
The drive is intended to be commanded by control input signals that
will start and stop the motor. A device that routinely disconnects
then reapplies output power to the motor for the purpose of starting
and stopping the motor should not be used. If it is necessary to
disconnect power to the motor while the drive is providing output
power, an auxiliary contact should be used to simultaneously
disable drive control run commands.