10-6 MD60 AC Drive User Manual
10.2 Troubleshooting Tables
Use the following tables to troubleshoot the drive. If you cannot
resolve the problem using these tables, contact Reliance Electric.
10.2.1 Problem: Drive Does Not Start From Terminal
Block Start or Run Inputs
Table 10.2 – Problem: Drive Does Not Start From Terminal Block Start or Run Inputs
Possible Cause(s) Indication Corrective Action
Drive is faulted Flashing red
FAULT LED
Clear fault by using one of
the following methods:
Press Stop
Cycle power
Set A100 (Fault Clear) to
1 (Clear Faults)
Cycle digital input if A051/
A052 (Digital Inx Select)
is set to option 7 (Clear
Fault).
Incorrect programming.
P036 (Start Source) is set
to option 0 (Keypad) or
option 5 (RS485 Port).
A051/A052 (Digital Inx
Select) is set to option 5
“Local” and the input is
active.
None Check parameter settings.
Incorrect input wiring. See
figure 6.2 for wiring
examples.
2-wire control requires
Run Forward, Run
Reverse or Jog input.
3-wire control requires
Start and Stop inputs
Stop input is always
required.
None Wire inputs correctly and/or
install jumper.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation MD60 and is the answer not in the manual?

Rockwell Automation MD60 Specifications

General IconGeneral
BrandRockwell Automation
ModelMD60
CategoryDC Drives
LanguageEnglish

Related product manuals