F-02
Deceleration
Time
(continued)
If
the
frequency
requested
from
the
keypad
(using
the
@â„¢
and
“W
keys)
is
less
than
the
maximum
speed
setting,
the
time
to
ramp
to
that
frequency
will
be
proportionally
less
than
the
actual
rate
setting.
For
example,
if
F-04 =
60Hz
and
F-02
=
4
seconds,
it
will
take
2
seconds
to
ramp
to
a
frequency
reference
of
0Hz
from
30
Hz.
Note
that
if
the
deceleration
rate
is
set too
fast,
a
high
bus
fault
may
occur
(HU
will
be
displayed)
F-03
Minimum
Speed
This
parameter
limits
the
speed
reference
to
the
drive.
Regardless
of
what
speed
reference
is
supplied,
the
regulator
will
not
command
a
speed
less
than
the
value
in
F-03.
Parameter
Range:
0.5
to
30
Hz
Default
Setting:
5.0
Hz
Step
Size:
0.10
Hz
if
F-04
< 100
Hz
0.25
Hz
if
F-04
= 100
Hz
ATTENTION:
The
SP500
drive
is
intended
to
operate
the
motor
ata
predetermined
minimum
speed
unless
disconnected
from
the
power
source.
The
user
is
responsible
for
assuring
safe
conditions
for
operating
personnel
by
providing
suitable
guards,
aucible
or
visual
alarms,
or
other
devices
to
indicate
that
the
drive
is
operating
at
minimum
speed,
(possibly
zero
speed),
or
the
user
must
verify
that
the
motor
output
shaft
will
rotate
at
all
combinations
of
load
and
output
speed
required
by
the
application.
F-04
Maximum
Speed
This
parameter
limits
the
speed
reference
to
the
drive.
Regardless
of
what
speed
reference
is
supplied,
the
regulator
will
not
command
a
speed
greater
than
the
value
in
F-04.
Parameter
Range:
30
to
240
Hz
Default
Setting:
60
Hz
Step
Size:
0.10
Hz
if
F-04
<
100
Hz
0.25
Hz
if
F-04
=
100
Hz
ATTENTION:
The
user
is
responsible
for
ensuring
that
driven
machinery,
all
drive-train
mechanisms,
and
process
line
material
are
capable
of
safe
operation
at
maximum
speed
(F-04).
Failure
to
observe
this
precaution
could
result
in
bodily
injury.