F-05
Current
Limit
This
parameter
limits
Parameter
Range:
10%
to
150%
of
rated
drive
current
motor
output
torque
on
°
while
it
is
running
or
Default
Setting:
150%
accelerating.
Step
Size:
1.0%
When
output
current
attempts
to
exceed
the
preset
current
limit,
motor
current
will
be
maintained
or
reduced,
or
the
acceleration
/
deceleration
time
will
be
extended.
If
current
limit
is
set
too
low
or
too high
relative to
the
required
load,
an
overcurrent
fault
may
occur
(OC
will
be
displayed).
F-06
Manual
Torque
Boost
This
parameter
sets
Parameter
Range:
0to
10%
the
percentage
of
a
3
output
voltage
boost
at
Default
Setting:
2%
zero
frequency.
Step
Size:
1%
Torque
boost
offsets
the
voltage
drop
of
the
AC
motor
at
low
speeds.
For
high
friction
loads
or
high
inertia
loads,
a
high
starting
torque
level
may
be
needed.
Manual
torque
boost
is
only
effective
at
speeds
lower
than
one-half
of
the
motors
base
frequency.
See
figure
8.1.
When
adjusting
this
parameter,
start
with
the
default
setting
of
2%
and
gradually
increase
the
value
until
motor
operation
is
satisfactory.
If
torque
boost
is
set
too high
relative
to
the
load
and
acceleration
rate,
an
overcurrent
fault
may
occur
(OC
will
be
displayed).
S100
<
9
5
50
e
3B
10
Manual
Torque
Boost
{
0
Base
Speed
Base
Speed
2
FREQUENCY
(Hz)
Figure
8.1
Manual
Torque
Boost
Adjustment
Range
F-07
V/Hz
(Base
Speed)
This
parameter
Parameter
Range:
30
to
240
Hz
specifies
the
base
oe
speed
at
maximum
Default
Setting:
60
Hz
output
voltage
and
is
Step
Size:
1.0
Hz
used
to
establish
the
volts/hertz
(V/Hz)
curve.
Programming
Reference
8-7