F-07
V/Hz
(Base
Speed)
(continued)
The
V/Hz
curve
allows
the
drive
to
maintain
a
constant
V/Hz
ratio,
providing
constant
torque
at
any
frequency.
See
figure
8.2.
100
|W
~ S
xt
&
©
=
L
g
=
ca
x
is
Ss
oF
We
3
6
Base
240
Frequency
FREQUENCY
(Hz)
Figure
8.2
—
Volts/Hertz
Curve
F-08
RPM
at
Base
Speed
This
parameter
scales
Parameter
Range:
10
to
9999
the
RPM
display
and
a
the setpoint
to
a
user-
Default
Setting:
1750
specified
engineering
Step
Size:
1.0
unit
unit.
This
parameter
defines
the
scaling
value
applied
to
the
current
speed
before
it
is
displayed.
It
is
also
used
to
scale
the
local
reference
when
F-18
is
set
to
ON.
The
value
to
enter
into
F-08
is
the
maximum
value
(in
RPM,
hertz,
or
any
other
engineering
unit)
to
be
displayed
when
the
drive
is
running
at
base
speed
(F-07).
Display
Scaling
Examples
Example
1:
Assume
that
an
application
requires
the
display
show
1750
RPM
when
the
drive
is
running
at
a
base
speed
of
60
Hz.
The
RPM
display
is
scaled
according
to
the
following
equation:
F-08
=
Di
|
07
Displayed
Value
Present
Operating
Speed
(Hz)
x
At
30
Hz,
the
RPM
display
will
show
875:
1750
_
30
(Hz)
x
60
7
875
Example
2:
Assume
the
application
requires
the
display
show
20
feet
per
minute
for
a
conveyor
(or
20
gallons
per
minute
for
a
pump)
when
the
motor
is
running
at
base
speed
(F-07=
60
Hz).
Enter
20
in
parameter
F-08
to
scale
the
display.
At
30
Hz,
the
display
will
show
10
feet
(or
gallons)
per
minute:
20
30
(Hz)
x
60"
=
10
8-8
SP500
AC
Drive
Installation
and
Operation
Manual
Version
3.1