F-11
Remote
Reference
Gain
(continued)
To
calculate
the
scaled
reference
if
you
are
using
a 0
to
20
mA
remote
reference,
use
the
following
equation:
Desired
Maximum
Reference
(MA)
x
199
-
%
gain
(mA
reference)
Reference
Range
(20)
Example
If
the
remote
speed
reference
is
0
to
20
mA
and
the
maximum
reference
required
is
19.2
mA,
scale
as
follows:
19.2
30"
x
100
=
96%
gain
To
calculate
the
scaled
reference
if
you
are
using
a 0
to
10
VDC
remote
reference,
use
the
following
equation:
Desired
Maximum
Reference
(VDC)
y
499
—
%
gain
(VDC
reference)
Reference
Range
(10)
Example
If
the
remote
speed
reference
is
0
to
10VDC
and
the
maximum
reference
required
is
9.5
VDC,
scale
as
follows:
9.5
_
ge,
cai
10
x
100
=
95%
gain
F-12
Remote
Reference
Offset
This
parameter
scales
Parameter
Range:
0%
to
40%
of
full
scale
minimum
reference
the
remote
speed
reference
(0 to
10VD
or
0
to
20
mA)
toa
minimum
value.
C
Default
Setting:
0%
Step
Size:
0.10%
Typically,
the
value
of
the
minimum
speed
reference
(the
amount
of
reference
at
minimum
speed,
F-03)
is
either
0
VDC
or
0
mA.
Enter
the
parameter
value
as a
percentage
of
the
full
scale
reference
to
be
offset
from
minimum
speed.
To
calculate
the
scaled
minimum
reference,
use
the
following
equation:
Desired
Minimum
Speed
Offset_
,
499
~
%
offset
Reference
Range
Scaling
Examples
Example
1:
If
the
remote
analog
input
speed
reference
is
0
to
20
mA
(J6
set
on
terminals
2
and
3),
and
the
available
analog
reference
signal
is
4
to
20
mA,
use
F-12
to
obtain
minimum
speed
with
minimum
analog
input
as
follows:
4
_
ono
30
x
100
=
20%
offset
Example
2:
If
the
remote
analog
input
speed
reference
is
0
to
10
VDC
(J6
set
on
terminals
1
and
2),
and
the
available
signal
is
offset
0.4
VDC,
use
F-12
to
obtain
minimum
speed
with
minimum
analog
input
as
follows:
a4
x
100
=
4%
offset
8-10
SP500
AC
Drive
Installation
and
Operation
Manual
Version
3.1