12-72
SP600 AC Drive User Manual
Displays elapsed hours since initial drive power up. This value will
roll over to 0 after the drive has been powered on for more than the
maximum value shown.
Selects alarm conditions that will initiate a drive alarm.
See table 12.3 for alarm descriptions.
242 Power Up Marker
Range: 0.0000 to 4,294,967.2925 Hr [0.0001 Hr]
Default: Read Only
Access: 2 Path: Utility>Faults
See also: 244, 246, 248, 250
32
259 Alarm Config 1
Range: See figure12.42
Default: See figure12.42
Access: 2 Path: Utility>Alarms
See also:
Figure 12.42 – Alarm Config 1 (259)
1
1
1
x
xxxxx
10 01234567891112131415
1=Enabled
0=Disabled
x =Reserved
Bit #
Factory Default Bit Values
UnderVoltage
Power Loss
Decel Inhibit
Nibble 1Nibble 2Nibble 3Nibble 4
x
x
1
Prechrg Actv
Anlg in Loss
IntDBRes OH
Drv OL Lvl 1
Drv OL Lvl 2
1111