Parameter Descriptions
12-71
Enables/disables annunciation of the faults shown in figure 12.41.
See table 13.6 for fault descriptions.
Resets a fault and clears the fault queue.
Enables/disables a fault reset (clear faults) attempt from any source.
This does not apply to fault codes stored in the fault queue, which
are cleared via other actions.
238 Fault Config 1
Range: See figure12.41
Default: See figure12.41
Access: 2 Path: Utility>Faults
See also:
Figure 12.41 – Fault Config 1 (238)
111xxxxxx
10 01234567891112131415
1=Enabled
0=Disabled
x =Reserved
Bit #
Factory Default Bit Values
UnderVoltage
Power Loss
Motor OverLd
Shear Pin
AutRst Tries
Decel Inhibit
Nibble 1Nibble 2Nibble 3Nibble 4
0
x
x
xx
0
0
240 Fault Clear
Range: 0 = Ready
1 = Clear Faults
2 = Clr Flt Que
Default: 0 = Ready
Access: 2 Path: Utility>Faults
See also:
241 Fault Clear Mode
Range: 0 = Disabled
1 = Enabled
Default: 1 = Enabled
Access: 2 Path: Utility>Faults
See also: