Example:
Calculate the maximum power of a 5 HP, 460V motor connected to a 480V rated
drive supplied with 342V Actual Line Voltage input.
Actual Line Voltage / Nominal Motor Voltage = 342/460 x 100% = 74.3%
•74.3%
×
5 HP = 3.7 HP
74.3%
×
60 Hz = 44.6 Hz
At 342V Actual Line Voltage, the maximum power the 5 HP, 460V motor can
produce is 3.7 HP at 44.6 Hz.
HP @ Motor (Drive Output)
Actual Line Voltage (Drive Input)
Full Power Range
Drive Operating Range
Nominal Motor Voltage -10%
Nominal Motor Voltage
Derated Power Range
No Drive
Output
Drive Rated Voltage
Drive Rated Voltage +10%
5 HP
3.7 HP
HP @ Motor (Drive Output)
Actual Line Voltage (Drive Input)
342V
460V
No Drive
Output
480V
528V