EasyManua.ls Logo

Rosemount 3095 - Page 60

Rosemount 3095
115 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rosemount Model 3095 Multivariable
Level Controller
5-4
Overrange Conditions Overrange conditions are typically caused by an error in which the
sensor or level measurements have reached an overrange condition
where substitute values are being used.
TABLE 5-3. Corrective Action:
Overrange Conditions.
Sensor Limits and Alarm
Abbreviation
Table 5-4 identifies sensor limits. Standard alarm abbreviations used
in alarm Tables 5-3 and 5-4 are:
LRL Lower Range Limits
URL Upper Range Limits
LRV Lower Range Value
URV Upper Range Value
URL+ URL + (10%URL)
(For example, URL+ = 250 + (0.10 3 250) = 275
LRL– LRL – (10%LRL)
(For example, LRL– = –250 –[0.10 3 (250)] = –275
TABLE 5-4. Level Controller
Sensor Limits.
(1) LRL– is equal to LRV and lower sensor trim limits.
(2) URL+ is equal to URV and upper sensor trim limits.
(3) In the fixed temperature mode, PT range is –459 to 3500 °F (–273 to 1927 °C).
(4) For Alpha Two field trial units, PT URL is 800 °F (427 °C).
Alarm text as displayed in
D
iagnostics, Error Info
Corrective Action
DP above URL+
These displays indicate that the device differential pressure reading exceeds its sensor limits by more than 10%.
There are two possible causes; either the device is overpressured (underpressured), or it has a sensor
malfunction. Check the pressure input to the device. If an overpressure (underpressure) condition exists, correct it.
If not, replace the sensor module as described on page 5-11.
DP below LRL–
Working Pressure above URL+
These displays indicate that the device absolute pressure reading exceeds its sensor limits by more than 10%.
There are two possible causes; either the device is overpressured (underpressured), or it has a sensor
malfunction. Check the pressure input to the device. If an overpressure (underpressure) condition exists, correct it.
If not, replace the sensor module as described on page 5-11.
Working Pressure below LRL
PT above URL+
Check the device RTD connector and RTD screw terminals to ensure that the RTD cable is properly connected.
Verify that the process temperature is between –40 °F and 1200 °F.
PT below LRL–
ST above URL+
These displays indicate that the ambient temperature limit of the device is being exceeded. Verify that the device
ambient temperature is between –40 °F and 185 °F. If device temperature exceeds these limits, correct the
temperature. If device temperature is within these limits, replace the sensor module as described on page 5-11.
ST below LRL
Sensor LRL–
(1)
LRL URL URL+
(2)
DP Range 2 –275 inH
2
0 at 68 °F –250 inH
2
0 at 68 °F 250 inH
2
0 at 68 °F 275 inH
2
0 at 68 °F
DP Range 3 –913 inH
2
0 at 68 °F –830 inH
2
0 at 68 °F 830 inH
2
0 at 68 °F 913 inH
2
0 at 68 °F
PT
(3)
–44 °F (–42 °C) –40 °F (–40 °C) 1200 °F (649 °C)
(4)
1220 °F (660 °C)
Sensor Temperature –44 °C –40 °C 85 °C 93.5 °C

Table of Contents

Related product manuals