5-9
Troubleshooting and Maintenance
TABLE 5-5. (continued).
Symptom Corrective Action
Sluggish Output
Response/Drift
IMPULSE PIPING
Check for leaks or blockage.
Ensure that blocking valves are fully open
Check for sediment in the device process flange.
Check for entrapped gas in liquid lines and for liquid in
gas lines.
Ensure that the density of fluid in impulse lines is unchanged.
Make sure that process fluid has not frozen within the
process flange.
DEVICE ELECTRONICS
Connect a Model 275 to check the sensor limits to ensure
calibration adjustments are within the sensor range and that
calibration is correct.
Confirm that damping is correctly set.
Confirm that the electronics housing is properly sealed
against moisture.
SENSING ELEMENT
The sensing element is not field repairable and must be
replaced if found to be defective. Check for obvious defects,
such as a punctured isolating diaphragm or fill fluid loss, and
contact your nearest Rosemount Service Center.
Confirm that the electronics housing is properly sealed
against moisture.