EasyManua.ls Logo

Rosemount 3144P - Page 58

Rosemount 3144P
170 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Reference Manual
00809-0100-4021, Rev FB
August 2011
Rosemount 3144P
3-28
HART
Hot Backup
To enable the Hot Backup feature of a 3144P transmitter with dual-sensor
option operating in conjunction with the HART Tri-Loop, ensure that the
output units of the sensors are the same as the units of the HART
Tri-Loop. Use any combination of RTDs or thermocouples as long as the
units of both match the units of the HART Tri-Loop.
Using the Tri-Loop to Detect Sensor Drift Alert
The dual-sensor 3144P transmitter sets a failure flag (through HART)
whenever a sensor failure occurs. If an analog warning is required, the HART
Tri-Loop can be configured to produce an analog signal that can be
interpreted by the control system as a sensor failure.
Use these steps to set up the HART Tri-Loop to transmit sensor failure alerts.
1. Configure the dual-sensor 3144P variable map as shown.
2. Configure Channel 1 of the HART Tri-Loop as TV (differential
temperature). If either sensor should fail, the differential temperature
output will be +9999 or –9999 (high or low saturation), depending on the
position of the Failure Mode Switch (see “Alarm Switch (HART)” on
page 2-4).
3. Select temperature units for Channel 1 that match the differential
temperature units of the transmitter.
4. Specify a range for the TV such as –100 to 100 °C. If the range is large,
then a sensor drift of a few degrees will represent only a small percent of
range. If Sensor 1 or Sensor 2 fails, the TV will be +9999 (high
saturation) or –9999 (low saturation). In this example, zero is the
midpoint of the TV range. If a T of zero is set as the lower range limit
(4 mA), then the output could saturate low if the reading from Sensor 2
exceeds the reading from Sensor 1. By placing a zero in the middle of
the range, the output will normally stay near 12 mA, and the problem will
be avoided.
5. Configure the DCS so that TV –100 °C or TV 100 °C indicates a
sensor failure and, for example, TV –3 °C or TV 3 °C indicates a drift
alert. See Figure 3-9.
Figure 3-9. Tracking Sensor Drift
and Sensor Failure with
Differential Temperature
Variable Mapping
PV Sensor 1 or Sensor Average
SV Sensor 2
TV Differential Temperature
QV As Desired
3 °C
0 °C
–3 °C
100 °C
Sensor Drift
Sensor Drift
Sensor Failure
(Failure Mode Switch HIGH)
DIFFERENTIAL
TEMPERATURE
Sensor Failure
(Failure Mode Switch LOW)
–100 °C
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China
sales@aotewell.com
+86-755-8660-6182

Table of Contents

Other manuals for Rosemount 3144P

Related product manuals