Table 7 Port Priorities and Default Baud Rates
NOTE 1: This means that if valid position data from external position sources are input on
both Sensor 1 and ECDIS port, the position data from Sensor 1 will be used.
NOTE 2: Output will be limited if baud rate is below 38400 bps. VDM and VDO messages will
not be output.
3.7.1 Output Drive Capacity for Serial Ports
Each serial port transmitter in the R5 SOLID can have a maximum of 25 listeners
consuming 2.0 mA each.
3.7.2 Input Load
Input impedance for each listener input is 6.4 kΩ.
3.7.3 Schematics of a R5 SOLID Serial Transceiver
Each of the RS422 serial interfaces on the R5 SOLID fulfils the requirements of IEC
61162-2 and IEC 61993-2. A detailed schematic of one of the serial ports in the R5
SOLID is shown below.
Figure 9 – Serial Port Schematics
3.7.4 R5 Signal Cable, DSUB-Open, 7000 118-078, B