4-167
1
2
3
4
5
6
7
8
3-WAY ECO-i SYSTEM Unit Specifi cations
7. Concealed Duct Type (U, US Types)
Unit specifi cations (F)
MODEL No.
Indoor Unit SPW-UR254GXH56(A/B)
POWER SOURCE
220 - 230 - 240 V, single-phase, 50/60 Hz
PERFORMANCE
Cooling Heating
Capacity
kW 7.3 8.0
BTU / h 25,000 27,000
Air circulation (Hi / Me / Lo) m
3
/ h 1,080 / 900 / 780
Moisture removal (High) Liters / h 3.5 –
External static pressure (High) Pa (mmAq) 50 (5.1): At shipment 92 (9.4): Using the booster cable
ELECTRICAL RATINGS
Voltage rating V 220 230 240 220 230 240
Available voltage range V 198 - 264 198 - 264
Running amperes A 0.83 0.86 0.89 0.78 0.81 0.84
Power input W 180 195 210 168 183 198
Power factor % 99 99 98 98 98 98
Max. starting amperes A 1 1 1 1 1 1
FEATURES
Controls Microprocessor
Timer ON / OFF Timer (Max. 72 hr)
Fan speeds 3 and Automatic control
Air fi lter Field supply
Refrigerant control Electronic expansion valve
Operation sound (
Hi / Me / Lo
) dB-A 34 / 30 / 27
Using the booster cable (Hi / Me / Lo) dB-A 38 / 34 / 30
Refrigerant tubing connections Flare type
Refrigerant tube
diameter
Narrow tube mm (in.) 9.52 (3/8)
Wide tube mm (in.) 15.88 (5/8)
Drain connection 25 A, OD32 mm
Drain pump Max. head 50 cm above drain connection
Remote controller Optional (Wired / Wireless)
Refrigerant tubing kit / Accessories Optional / Booster cable
Color (Approximate value) –
DIMENSIONS & WEIGHT
Unit dimensions
Package dimensions
Unit dimensions
Height mm (in.) 310 (12-7/32) 358 (14-3/32)
Width mm (in.) 1000 (39-3/8) 1191 (46-7/8)
Depth mm (in.) 630 (24-13/16) 783 (30-13/16)
Net weight kg (lbs.) 32 (71)
Shipping weight kg (lbs.) 37 (82)
Shipping volume m
3
(cu.ft) 0.334 (11.8)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27°C DB / 19°C WB; Outdoor air temperature 35°C DB
Heating: Indoor air temperature 20°C DB; Outdoor air temperature 7°C DB / 6°C WB