4-330
1
2
3
4
5
6
7
8
3-WAY ECO-i SYSTEM Unit Specifi cations
10. Concealed Floor-Standing Type (FM Type)
10-1. Specifi cations
Unit specifi cations (A)
MODEL No.
Indoor Unit SPW-FMR74GXH56(A/B)
POWER SOURCE
220 - 230 - 240 V, single-phase, 50/60 Hz
PERFORMANCE
Cooling Heating
Capacity
kW 2.2 2.5
BTU / h 7,500 8,500
Air circulation (Hi / Me / Lo) m
3
/ h 420 / 360 / 300
Moisture removal (High) Liters / h 1.0 –
ELECTRICAL RATINGS
Voltage rating V 220 230 240 220 230 240
Available voltage range V 198 - 264 198 - 264
Running amperes A 0.24 0.25 0.26 0.17 0.18 0.19
Power input W 51 56 61 36 40 45
Power factor % 97 97 98 96 97 99
Max. starting amperes A 1 1 1 1 1 1
FEATURES
Controls Microprocessor
Timer ON / OFF Timer (Max. 72 hr)
Fan speeds 3 and Automatic control
Air fi lter Washable, easy access
Refrigerant control Electronic expansion valve
Operation sound (
Hi / Me / Lo
) dB-A 33 / 30 / 28
Refrigerant tubing connections Flare type
Refrigerant tube
diameter
Narrow tube mm (in.) 6.35 (1/4)
Wide tube mm (in.) 12.7 (1/2)
Drain connection 20 A, OD26 mm
Remote controller Optional (Wired / Wireless)
Refrigerant tubing kit / Accessories Optional / –
Color (Approximate value) Munsell 10Y 9.3 / 0.4, RAL 9010-GL
DIMENSIONS & WEIGHT
Unit dimensions
Package dimensions
Unit dimensions
Height mm (in.) 616 (24-1/4) 679 (26-23/32)
Width mm (in.) 904 (35-19/32) 976 (38-7/16)
Depth mm (in.) 229 (9-1/32) 312 (12-9/32)
Net weight kg (lbs.) 21 (46)
Shipping weight kg (lbs.) 23 (51)
Shipping volume m
3
(cu.ft) 0.207 (7.3)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27°C DB / 19°C WB; Outdoor air temperature 35°C DB
Heating: Indoor air temperature 20°C DB; Outdoor air temperature 7°C DB / 6°C WB
TD831143-00W-3WAY.indb330TD831143-00W-3WAY.indb330 2008/12/0117:25:052008/12/0117:25:05