Control of 3-WAY ECO-i SYSTEM
1
2
3
4
5
6
7
8
6. Simplifi ed Remote Controller
Test run setting
1.
• “TEST” will appear on the display during test run.
• During test run, temperature cannot be adjusted. This button should be used only for test run.
2.
3.
Press both and buttons on the remote controller for more than 4 seconds together,
and then press (ON/OFF) button.
Perform test run in any operation mode of “heat”, “cool” or “fan”.
The outdoor unit does not operate for 3 minutes after stopping operation or turning on the unit.
After test run is finished, press both and buttons again for more than 4 seconds together,
and then make sure “TEST” goes off from the display. (The 60-minute off timer function is provided
for this remote controller in order to avoid continuous test run.)
Caution
To install the remote controllers side-by-side, keep the space between each for more than 75 mm.
(See Fig. 3-72-2)
Install the remote controller more than 70 mm apart from the corner of the wall.
(See Fig. 3-72-2)
*1
*2
To install the remote controllers one above the other, keep the space between each for more than 25 mm.
(See Fig. 3-72-3)
*3
Caution when installing the remote controller (See Fig. 3-72-1)
17
70
120
66.8
116.8
10
4.4
83.5
33.4
Unit: mm
16.6
13
33.5
16.7
9.4
4.4
5.4
9.4
8
Fig. 3-72-1
Fig. 3-72-2 Fig. 3-72-3
(*1) (*2)
(*3)
NOTE