(B)
(F)
Top view
Top view
(A)
(B)
(A)
(B) (B)
(C) (C)
(C)
(D)
(E)
(B)
(B)
(C) (C)
(D)
(F)
(E)
(B)
When transporting the unit, have it delivered as close
to the installation site as possible without unpacking.
Use a hook for suspending the unit. (Fig. 4-11)
Fig. 4-11
When hoisting the outdoor unit, pass ropes or straps
under the bottom plate as shown in the figure above.
When hoisting, the angle between the rope and top
panel must be 70° or greater so that the rope does not
come into contact with the fan guard. (Use 2 lengths
of rope 7.5 meters long or longer.)
When passing the ropes through the square holes of
the bottom plate:
Place the rope in the outer edge of the square holes.
Use protective panels or padding at all locations where
the rope contacts the outer casing or other parts to
prevent scratching. In particular, use protective mate-
rial (such as cloth or cardboard) to prevent the edges
of the top panel from being scratched.
Be careful of the fan.
There is danger of injury if the fan starts to turn during
inspection. Be sure to turn OFF the remote power
switch before beginning inspection.
4-11. Installing the Outdoor Unit
(1) Use anchor bolts (M12) or similar to securely anchor
the unit in place. (Fig. 4-12)
(100)
(100)
88
20
50
The vibration insulator, base, or platform must be large
enough to bear the full surface of the base plate legs.
Fig. 4-12
(2) Be sure the rubber vibration insulator and platform ex-
tend to the inside of the legs. In addition, the washers
used to anchor the unit from the top must be larger than
the installation anchor holes. (Figs. 4-12 and 4-13)
38.5
15
50
Fig. 4-13
Fig. 4-14
(Detailed view of legs)
Surface where
installation anchor
brackets are installed
Unit: mm
Vibration insulator
Base
Washer
Plate leg
Anchor bolts
Unit: mm
890 (
Top
plate dimensions)
790 (Installation hole pitch)
890
(
To p
plate dimensions)
920 (Installation hole pitch)
950 (Maximum dimensions)
(Positions where anchor bolts are fastened)
Installation anchor hole (4 – 15 × 20 oval holes)
Unit: mm
(A)
2870
(D)
2770 (Installation hole pitch)
(B)
890 (Top plate dimensions)
(E) 920 (Installation pitch)
(C)
790 (Installation hole pitch)
(F)
950 (Maximum dimensions)
(A)
1880 (Top
plate
dimensions)
(D)
1780 (Installation hole pitch)
(B)
890 (Top
plate
dimensions)
(E) 920 (Installation pitch)
(C)
790 (Installation hole pitch)
(F)
950 (Maximum dimensions)
4-10. Transporting
CAUTION
4 – 15 × 20 hole
2-39
Design of 3-WAY ECO-i SYSTEM
1
2
3
4
5
6
7
8
4. Installation Instructions
TD831143-00W-3WAY.indb39TD831143-00W-3WAY.indb39 2008/12/0116:15:502008/12/0116:15:50