4-299
1
2
3
4
5
6
7
8
3-WAY ECO-i SYSTEM Unit Specifi cations
8. Concealed Duct High Static Pressure Type (D Type)
8-1. Specifi cations
Unit specifi cations (A)
MODEL No.
Indoor Unit SPW-DR254GXH56(A/B)
POWER SOURCE
220 - 230 - 240 V, single-phase, 50/60 Hz
PERFORMANCE
Cooling Heating
Capacity
kW 7.3 8.0
BTU / h 25,000 27,000
Air circulation (Hi / Me / Lo) m
3
/ h 1,380 / 1,320 / 1,260
Moisture removal (High) Liters / h 3.1 –
External static pressure (High) Pa (mmAq) 186 (19)
ELECTRICAL RATINGS
Voltage rating V 220 230 240 220 230 240
Available voltage range V 198 - 264 198 - 264
Running amperes A 2.29 2.30 2.31 2.29 2.30 2.31
Power input W 480 505 530 480 505 530
Power factor % 95 95 96 95 95 96
Max. starting amperes A 3 3 3 3 3 3
FEATURES
Controls Microprocessor
Timer ON / OFF Timer (Max. 72 hr)
Fan speeds 3 and Automatic control
Air fi lter Field supply
Refrigerant control Electronic expansion valve
Operation sound (
Hi / Me / Lo
) dB-A 44 / 43 / 42
Refrigerant tubing connections Flare type
Refrigerant tube
diameter
Narrow tube mm (in.) 9.52 (3/8)
Wide tube mm (in.) 15.88 (5/8)
Drain connection 25 A, Male screw
Remote controller Optional (Wired / Wireless)
Refrigerant tubing kit / Accessories Optional / –
Color (Approximate value) –
DIMENSIONS & WEIGHT
Unit dimensions
Package dimensions
Unit dimensions
Height mm (in.) 420 (16-17/32) 513 (20-3/16)
Width mm (in.) 1065 (41-15/16) 1148 (45-3/16)
Depth mm (in.) 620 (24-13/32) 713 (28-1/16)
Net weight kg (lbs.) 47 (104)
Shipping weight kg (lbs.) 61 (134)
Shipping volume m
3
(cu.ft) 0.420 (14.8)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27°C DB / 19°C WB; Outdoor air temperature 35°C DB
Heating: Indoor air temperature 20°C DB; Outdoor air temperature 7°C DB / 6°C WB
TD831143-00W-3WAY.indb299TD831143-00W-3WAY.indb299 2008/12/0117:24:512008/12/0117:24:51