200
150
0
L
H
250
50
100
100
50
250
H
L
0
150
200
SPW-GU055XH
Air charge Air discharge
400 500 600
External Static Pressure (Pa)
400 500 600
300
200
150
400
350
0
600 900800700
L
H
250
50
100
600 900800700
L
H
SPW-GU075XH
How to Read the Diagram
The vertical axis is the EXTERNAL STATIC PRESSURE (Pa) while the horizontal axis represents the AIR FLOW (m
3
/h).
The characteristic curve for the “H” and “L fan speed control are shown. The name plate values are shown based of the
“H” air flow. Therefore in the case of the SPW-GU055XH the flow is 500 m
3
/h, while the EXTERNAL STATIC PRESSURE
is 183 Pa at “H” position (Air charge side). If the external static pressure is too low (due to short duct), the air flow volume
may be too great at each air outlet. To set the fan speed control to “L” position, use the supplied external static pressure
line switching connector. (Refer next page)
External Static Pressure (Pa)
Air charge Air discharge
300
200
150
400
350
0
250
50
100
Air Flow Volume (m
3
/h)
Air Flow Volume (m
3
/h)
Air Flow Volume (m
3
/h)
Air Flow Volume (m
3
/h)
External Static Pressure (Pa)
External Static Pressure (Pa)
4-366
1
2
3
4
5
6
7
8
3-WAY ECO-i SYSTEM Unit Specifi cations
12. Total Heat Exchanger with DX coil (GU Type)
12-5. Indoor Fan Performance
TD831143-00W-3WAY.indb366TD831143-00W-3WAY.indb366 2008/12/0117:25:212008/12/0117:25:21