Operators Handbook DCU3 – System
6., Main function „Control Loops“
BAEDCU3 - Rev. 4.6 - 0504 6 - 5
6.4.3 Operating Display
Tag Entry Displayed value or function, required input
MIN % Input of minimum output limit, representing the setpoint minimum for
the servo controller (0 ... 100 % = measuring range of process value)
MAX % Input of minimum output limit, representing the setpoint minimum for
the servo controller (0 ... 100 % = measuring range of process value)
DEADB [PV] Input of deadband; physical unit depending on process value
XP % Input of proportional range in [%] of the measuring range
(100 % = maximum measuring range of process value)
TI sec Input of reset time
TD sec Input of rate (delay) time
Process
Value
Selection of intended process value for control if double measurements
are applied