Operators Handbook DCU3 – System 
 
6., Main function „Control Loops“ 
BAEDCU3 - Rev. 4.6 - 0504    6 - 12 
6.9 pO
2
-Control Methods 
Contrary to the other controls of fermentor systems (temperature, pH etc.) the pO
2
 - control is adapted 
to the specific process requirements. For this the DCU3 - system comprises different pO
2
 - controllers 
that can be implemented according to the selected process. These control strategies can be realized: 
  pO
2
 - cascade control with the following possible servo controllers: 
– Stirrer 
–  Airflow (Massflow Controller) 
– Substrate 
– Pressure  
–  Gasmix (pulsed valves) 
–  Gasflow Ratio (two Massflow-Controllers with O
2
-enrichment) 
The controller configuration can be especially matched to the fermentor system and process. Several 
of the above controllers can be implemented. Besides the controllers mentioned above, customized 
DCU configurations with other pO
2
 - control strategies can be realized. 
6.10 pO
2
 - Cascade Controller with 3 Servo Controllers 
In the cascade system the pO
2
-controller is the master controller. Its output directly triggers the set-
point input of the servo controller.  
Optionally a sequential mode can be selected for the pO
2
-cascade control. Then the pO
2
 - controller 
triggers two or three servo controllers sequentially, in order of their priority. In the pO
2
 - controller you 
can define a specific „MIN/MAX“ range for the setpoint signal transmitted to each servo controller: 
  When the pO
2
 control is switched on, at first the output of the pO
2
 controller operates the 
setpoint input of the priority 1 - servo controller (CASC1). Optionally defined servo control-
lers 2 and 3 get the setpoint, which is defined as „MIN“ in the pO
2
 controller. 
  At increase of O
2
-consumption, when the setpoint output of the 1st servo controller reaches 
its „MAX“ limit, the output of the pO
2
 controller is automatically switched over to the priority 2 
- servo controller (CASC2). The user can adjust the delay time for switching-over, default 
delay time is 5 minutes. Then the outputs are controlled as follows:  
–  servo controller 1:  the predefined „MAX“ - output 
–  servo controller 2:  controlled output of the pO
2
-controller 
–  servo controller 3:  the predefined „MIN“ - output 
  After switching over to the 3rd servo controller, the outputs are controlled as follows: 
–  servo controller 1:  the predefined „MAX“ - output 
–  servo controller 2:  the predefined „MAX“ - output 
–  servo controller 3:  controlled output of the pO
2
-controller 
  If the O
2
-consumption decreases the controller setting is switched back in reverse order. 
Such a control strategy allows to keep the pO
2
 value constant over prolonged periods of the process 
without further manual intervention. The PID parameters for servo controllers of priority 1, 2 and 3 can 
be adjusted independently of each other in order to allow maximum adaptation to the process-
dependent behavior of the control system.