12
Pulse configuration
Attribute Name Attribute Type Value/Range M/O/C
Comments
cmdQual ENUMERATED pulse | persistent M
For boGGIO pulse output,
a relay must be set to
pulse mode via the device
Relay Setup
onDur INT32U
M boGGIO class nodes:
default = 2000 ms
CSWI class nodes:
default = 0
offDur INT32U
M Not supported
numPls INT32U 1 M Read only
Originator
Attribute Name Attribute Type Value/Range M/O/C Comments
orCat ENUMERATED not-supported | bay-control |
station-control | remote-control
| automatic-bay | automatic-
station | automatic-remote |
maintenance | process
M
orIdent OCTET STRING64 M
Unit definition
Attribute Name Attribute Type Value/Range M/O/C Comments
SIUnit ENUMERATED See IEC61850-7-3, Tables A.1
to A.4 in Annex A
M
multiplier ENUMERATED See IEC61850-7-3, Table A.5 in
Annex A
O
The default value of the multiplier is 0 and the multiplier value is 1: 10**0 = 1.
Vector
Attribute Name Attribute Type Value/Range M/O/C Comments
mag AnalogueValue M Only one of the attributes
of the AnalogueValue may
be present for a given
instance of DATA.
ang AnalogueValue O ang attribute is used for
data objects of the
phzrMMXU LN only (see
below)
Point definition
Common data attribute class is not supported.
CtlModels definition
Attribute Value Comments
status-only Not controllable SPS, DPS and INS
direct-with-normal-security Controllable SPC. Supported by boGGIO and evfGGIO class nodes.
sbo-with-normal-security Controllable SPC. Supported by boGGIO and evfGGIO class nodes.
direct-with-enhanced-security Controllable DPC. Supported by CSWI class nodes.
sbo-with-enhanced-security Not supported
SboClasses definition
Attribute Value Comments
operate-once
operate-many Not supported