46
6.5 Configuring the GOOSE Publisher
The PM180 GOOSE publisher provides the dedicated dataset CTRL/LLN0$DSetGOOSE1 for
GOOSE communications. The default dataset variables list can be modified via the IEC 61850
Datasets setup (see Section 6.3).
To configure the GOOSE publisher:
1. Select IEC 61850 Setup from the Meter Setup menu, and then click on the GOOSE
Publisher Setup tab.
2. Configure the destination MAC address, application ID and the maximum message
retransmission interval as required for your application. Other setup attributes are not
changeable and are indicated for information only.
3. Select Yes in the Publisher Enabled box to enable publisher operation.
4. Send your setup to the device.
6.6 Configuring the GOOSE Subscriber
The PM180 can be subscribed to messages sent by any GOOSE network device including
both PM180 and non-SATEC devices.
The GOOSE subscriber supports up to 20 subscriptions with up to 16 data elements in each
subscription. The location of the subscribed elements in GOOSE data sets and mapping to
the PM180 internal variables are configurable. The subscription elements are selected from a
publishing device’s ICD/CID file.
The PM180 provides a set of internal variables for mapping external GOOSE data: