52
IED properties
Datasets
Report control blocks
GOOSE publisher setup
To create or update a device CID file:
1. Click the "Update CID file" button on the setup tab.
2. Locate a source ICD or CID file for your device you wish to update and
click Open. Use the PM180.icd file provided with your device as a primary
template file to create a new CID file, and then use your new file as a
source to update remaining settings.
3. Select the folder and the name of the target CID file where to store
your new configuration description and click Open. It may be the same CID
file you used as the source.
4. Repeat this procedure for other configuration setups you wish to update.
NOTES
In the event an RCB reference is used as the Report ID (the default setting for non-
indexed RCBs), update the RCBs in a CID file after changing the IED name even if no
changes to RCBs have been made to keep consistency with your device.
Breaker/switch nodes prefixes are configured in a CID file as they are defined in the
device database while updating the IED properties. If you change the default
breaker/switch prefixes in your device via the Bay Control setup, save the setup to
the device database, and then update the IED properties in a CID file even if no
other properties have been changed.

Table of Contents