SPN CID SID PID PPID FMI
John Deere
Volvo
Perkins
Description Comment
1172
Input temperature of the TGV
compressor
3
Input voltage of the temperature sensor
high
Short to V+
4
Input voltage of the temperature sensor
low
Short to V-
1180 Input temperature of the TGV turbine
0
Turbine temperature extremely high Short to V+
16 Turbine temperature moderately high Short to V-
1184 173 Exhaust gas temperature sensor
1239 96
Status of the pressure system of the
common rail
1347 Pump control valve status
Pump control valve #1
status for 6081HF070
3 Pump control valve current high
5 Pump control valve error/mismatch
7 Fuel rail pressure control error
10 Pump control valve fuel flow not detected
1348 Pump control valve #2 status Only for 6081HF070
5 Pump control valve #2 error/mismatch
10
Pump control valve #2 fuel flow not
detected
1485 1485 5 Pump power relay status
ECU main relay of VOLVO
EMS/EDC
2 Pump power relay fault
3
ECU main relay short circuit
high
1568 Torque curve selection
2 Torque curve selection invalid
4 Torque curve input voltage high
9 Torque curve selection missing
SPN CID SID PID PPID FMI
John Deere
Volvo
Perkins
Description Comment
1569 Fuel supply status
31 Fuel de rate
1639 Fan speed
1 Fan speed zero or absent
2 Fan speed signal erratic
16
Fan speed more than 300 rpm above its
setpoint for at least 180s
18
Fan speed more than 300 rpm below its
setpoint for at least 180s
2000 ECU status
6 Vehicle ID missing
13 Security violation
281/285