8.0 Turning on the Panel
8.1 Before Connecting the Power
1. To prevent sparking, do not connect the batteries. Connect the batteries after powering
the system from the main AC supply.
2. Check that all modules are installed in the proper location with the proper connections.
3. Check all field (external) wiring for opens, shorts, and ground.
4. Check that all interconnection cables are secure, and that all connectors are plugged in
properly.
5. Check all jumpers and switches for proper setting.
6. Check the AC power wiring for proper connection.
7. Check that the chassis is connected to EARTH GROUND (cold water pipe or ground
rod).
8. Make sure to close the front cover plate before powering the system from main AC
supply.
8.2 Power-up procedure
After completing the steps in 8.1 above:
1. Plug in the AC power.
The A.C. ON LED illuminates, the TRBL LED flashes, and the buzzer sounds.
2. Press the SYSTEM RESET button.
The buzzer continues to sound and the TRBL LED continues to flash.
3. Connect the batteries as shown in Figure 26 below. Observe the correct polarity: the red
wire is positive (+) and black wire is negative (í).

Table of Contents

Other manuals for Secutron MR-2300T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Secutron MR-2300T and is the answer not in the manual?

Secutron MR-2300T Specifications

General IconGeneral
BrandSecutron
ModelMR-2300T
CategoryControl Panel
LanguageEnglish

Related product manuals