Table 12 Settings permitted in CAN/ULCS527
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED
PARTIES
This product incorporates field-programmable software. In order for the product to comply with the
requirements in CAN/ULCS527, Standard for Control Units for Fire Alarm Systems, certain programming
features or options must be limited to specific values or not used at all as indicated below.
Program feature or
option
Permitted in CAN/
ULCS527? (Y/N)
Possible settings\methods
Settings permitted in
CAN/ULCS527
Account Reporting
Format (see page 82
and page 83)
Y Contact ID, SIA 300, SIA 110
Contact ID if
connected to a DSC
transmitter
Manual Signal Silence
(see page 65)
Y Enabled, Disabled Enabled
Auto Signal Silence
Timer (see page 67)
Y
Disabled, 5, 10, 15, 20, 30
minutes
Disabled for NAC
circuits for dwelling
units, all settings are
allowed for other
NACs
Signal Isolators (see
page 68)
Y Enabled, Disabled
Enabled only when
suite isolators are
used
Signal Rate (see
page 68)
Y
Temporal, Continuous, March
Time, California
Tem por al
Active EOL (see
page 68)
Y Enabled, Disabled
Enabled if using an
active EOL resistor or
MR-2300-A
Supervisory Circuit
Type (see page 51)
Y Latching, Non-latching Latching
Aux Disconnect
disconnects Common
Alarm and Common
Supervisory (see
page 67)
Y Enabled, Disabled Disabled
Dialer Operation Mode
(see page 85)
Y (U)DACT, DACT (U)DACT
AC Loss Delay (see
page 82)
Y 0 to 20 hours 0 to 3 hours
Cellular Report Date
and Auto Test Time
(see page 87)
Y Day of month and Time of day
Set Cellular Report
Date to 0
Set Auto Test Time to
3:00 (see page 87)