EasyManua.ls Logo

Secutron MR-2300T

Secutron MR-2300T
107 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
46
9.2 Indicating Circuit Indicators
The panel has 1 indicator for each of the 12 initiating circuits (shown in Figure 27). Each
indicator has a button and 2 LEDs, shown in Figure 28.
Figure 28 Alarm Circuit Indicator
The Circuit Disconnect Button is described in section 9.5 on page 50. The LEDs are described
in the 4 sections below.
9.2.1 Alarm Circuit Indicators
Table 6 applies to Initiating Circuits configured as Verified Alarm, Non-Verified Alarm, Water
flow Alarm, Sprinkler Alarm, or General Alarm Circuits.
9.2.2 Supervisory Circuit Indicators
This operation applies to Initiating Circuits configured as Latching or Non-Latching
Supervisory Circuits. The following table summarizes the indications in response to different
events.
Table 6 Alarm Circuit Indicators
Event Circuit Status LED Configuration
Circuit in Alarm Steady (red)
Pre-alarm Fast flash rate (red)
Verified Alarm
Sprinkler Alarm
Water flow Alarm
Activated circuit reconnected (when you
press the Disconnect button a second
time)
Fast flash rate (red) for 5
seconds to indicate a
pending alarm
Event Circuit Trouble LED Configuration
Open circuit (Class B)
Flashes at the trouble rate
(amber)
Verified Alarm
Non-Verified Alarm
Water flow Alarm
Sprinkler Alarm
General Alarm
Open circuit or Class A trouble
Flashes at the trouble rate
(amber)
Disconnected (Class A)
Flashes at the trouble rate
(amber)
Circuit in Alarm OFF
Table 7 Supervisory Circuit Indicators
Event Circuit Status LED Configuration
Circuit in Alarm Steady (amber)
Latching Sup.
Non-Latching Sup.
ZONE-1
DISCO NNE CT
Circuit Status LED
Circuit Trouble LED
Circuit
Disconnect
Button

Table of Contents

Related product manuals