56
• If the panel is not already in General Alarm and if the AUTOMATIC ALARM SIGNAL
CANCEL LED is on steady, indicating that the Auto General Alarm Timer has been
acknowledged, the timer is restarted and the AUTOMATIC ALARM SIGNAL CANCEL
LED is extinguished (or blinks if it has been configured to blink).
A Second Stage Alarm (General Alarm) when the panel is already in alarm causes the
following:
• The buzzer sounds steadily.
• All non-disconnected signals are activated at the evacuation rate.
• If the SIGNAL SILENCE LED is on, it is turned off and the Auto Signal Silence Timer, if
configured, is restarted.
• The AUTOMATIC ALARM SIGNAL CANCEL LED if on, is turned off.
Alarm inputs are latching, which means that they remain active until the SYSTEM RESET
button is pressed. Note that if the system is configured for Correlations, any Second Stage/
General Alarm (caused by the Auto General Alarm Timer, the GENERAL ALARM button on
the Front Panel or Remote Annunciator, or by a General Alarm Initiating Circuit) condition
activates ALL Indicating Circuits, whether they are correlated or not.