Features Standard Features/Lift Switch Inputs - Additive
______________________________________________________________________________
MillipaK PUMP Controller Manual Page 26 07/11/05
Lift Switch Inputs - Additive
Lift input switches 5 to 7 may be configured as Additive. As the name implies if two or more
switches configured as additive are active together then the speed demand set for each switch will
be added together and this will be the final speed demand.
Additive also applies if a priority and an additive switch are active simultaneously.
For example if lift accelerator 1 input demand is at 20%, switch 3 is active with its maximum
speed personality set to 20% and switch 5 is active and programmed as additive and with a speed
setting of 30 % then the final demand would be 50% (lift accelerator 1 demand + switch 5
demand).