Features Standard Features/Seat Switch
______________________________________________________________________________
MillipaK PUMP Controller Manual Page 28 07/11/05
Seat Switch
A seat switch can be configured via the digital I/O configuration. If setup menu option seat switch
cuts pump is configured to on, and the seat switch is opened, and the seat switch timer has timed
out the controller will stop pulsing and a seat fault will be indicated. Before pulsing can be
restarted the seat switch must be closed. The time period is programmed by means of the
Calibrator (Seat Switch Delay).
Immediate Seat Delay
Calibrator Menu Reference:
11.02
Minimum Maximum Step Size Typical Value
0.1S 5.0S 0.1S 5.0S
Power On Seat Cuts Pump
Calibrator Menu Reference:
12.04
Options Typical Value
OFF ON OFF