40
[Input error indication]
Output
status
when input
errors occur
(*1)
Contents
and
Indication
Output status
Controller/Converter
Controller Converter
OUT1 OUT2 OUT1
Direct action Reverse action
Direct Reverse Direct Reverse
flashes.
ON (20 mA)
or OUT1 high
limit value (*2)
OFF (4 mA)
or
OUT1 low limit
value
OUT2
low limit value
20 mA
or
OUT1
high
limit value
4 mA
or
OUT1
low
limit value
OFF (4 mA)
or OUT1 low
limit value
flashes.
OFF (4 mA)
or
OUT1 low
limit value
ON (20 mA)
or
OUT1 high limit
value (*2)
OUT2
low limit value
4 mA
or
OUT1
low
limit value
20 mA
or
OUT1
high
limit value
OFF(4 mA) or
OUT1 low limit
value
(*1) [Output status when input errors occur] can be used only for controllers using direct current
and voltage inputs, and direct current output. If OUT is not Direct current output, the output
status will be the same as when is selected in [Output status when input errors
occur]. For manual control, the preset MV is output.
(*2) Outputs a value between OFF (4 mA) and ON (20 mA) or between OUT1 low limit value
and OUT high limit value, depending on deviation.
Thermocouple, RTD input
Input Input range Indication range Control range
KT
–199.9 to 400.0 –199.9 to 450.0 –205.0 to 450.0
–199.9 to 750.0 –199.9 to 850.0 –209.0 to 850.0
Pt100
–199.9 to 850.0 –199.9 to 900.0 –210.0 to 900.0
–200 to 850 –210 to 900 –210 to 900
–199.9 to 999.9 –199.9 to 999.9 –211.0 to 1099.9
–300 to 1500 –318 to 1600 –318 to 1600
JPt100
–199.9 to 500.0 –199.9 to 550.0 –206.0 to 550.0
–200 to 500 –207 to 550 –207 to 550
–199.9 to 900.0 –199.9 to 999.9 –211.0 to 999.9
–300 to 900 –312 to 1000 –312 to 1000
Indication range and Control range for thermocouple inputs except above:
[Input range low limit value 50 (100 )] to [Input range high limit value + 50 (100 )]
DC input
Indication range: [Scaling low limit value Scaling span x 1%] to [Scaling high limit value
+ Scaling span x 10%]
However, if the input value is out of the range –1999 to 9999, the PV
Display flashes or ”.
Control range: [Scaling low limit value Scaling span x 1%] to [Scaling high limit value
+ Scaling span x 10%]
DC input disconnection
When DC input is burnt out, the PV Display flashes for 1 to 5 V DC and 4 to 20 mA
DC inputs, and for 0 to 1 V DC input.
For 0 to 5 V DC, 0 to 10 V DC and 0 to 20 mA DC inputs, the PV Display indicates the
value corresponding with 0 V or 0 mA input.