14.5.3 PROFINET Conformance Class
The device complies with PROFINET Conformance Class B (CC-B) and supports the
properties defined within.
Further information on the PROFINET Conformance Classes can be found in the docu‐
ment of the PI user organization (PROFIBUS and PROFINET International).
You can find the document in the “Downloads” area at:
www.profibus.com
14.5.4 General requirements on a switch suitable for PROFINET applications
For PROFINET Conformance Class B and C (CC-B / CC-C), a PROFINET-certified switch
which can be configured as a PROFINET device must be used.
For further information, refer to the commissioning guidelines of the PI “Installation
Guideline PROFINET Part 2: Network Components”.
You can find the document in the “Downloads” area under:
www.profibus.com
14.5.5 Notes on installing the SICK bar code scanner into a PROFINET network
For 1-port devices, these include:
LLDP (neighborhood detection)
1)
I&M 0-4 (device identification)
1)
Device exchange by topology check
1)
16 bit digital “status word” for reading gate result
16 bit digital “control word” for controlling the device via PLC
Heartbeat (for checking communication)
GSD file for configuring the device using modules via the PLC
1)
For 2-port devices, these include:
LLDP (neighborhood detection)
1)
I&M 0-4 (device identification)
1)
Device exchange by topology check
1)
MRP (ring redundancy)
1)
16 bit digital “status word” for reading gate result
16 bit digital “control word” for controlling the sensor via PLC
Heartbeat (for checking communication)
GSD file for configuring the sensor using modules via the PLC
1)
14.5.6 Behavior of the switching outputs of the bar code scanner with “Fieldbus input” reading cycle
source
The digital outputs can be configured so that they can show information from other net‐
work participants (e.g. external output 1 = fieldbus input).
In the event that a fieldbus is interrupted, these outputs are no longer updated and
keep the last value that existed before the interruption.
After switching on the fieldbus (power-up), all digital outputs are set to their “passive”
values.
Status of digital outputs with output value behavior
IOPS = Bad Contain the last value before cancellation
Connection lost Contain the last value before cancellation
1)
Properties of the CC-B
14 APPENDIX
66
O P E R A T I N G I N S T R U C T I O N S | CLV61x DualPort (PROFINET) 8017842/ZOK7/2019-02-01 | SICK