The reset must only be possible, when all safety functions and protective devices are
f
unctional.
The reset of the protective device must not introduce any movement or dangerous situ‐
ations itself. The machine is only permitted to start after the reset once a separate start
command has been sent.
Manual resets are performed using a separate, manually operated device, such as
a reset pushbutton.
Automatic resets by the protective device are only permitted in special cases, if
one of the following conditions is met:
°
It must not be possible for people to be in the hazardous area without trigger‐
ing the protective device.
°
It must be ensured that no people are in the hazardous area during or after
the reset.
Internal restart interlock
Eac
h safety output of the safety laser scanner is equipped with a configurable internal
restart interlock.
With safety outputs via the network, resetting is done via a network signal.
When the internal restart interlock is used, the following sequence is the result for the
machine operator:
1 A safety output of the safety laser scanner switches to the OFF state if there is an
interruption in the protective field.
2 The safety output remains in the OFF state when there is no longer an object in
the protective field.
3 The safety output only switches back to the ON state when the operator presses
the reset pushbutton, which is outside the hazardous area. If there is an object in
the protective field when the reset pushbutton is pressed, the safety output stays
in the OFF state.
4 After the reset, the operator can restart the machine in a second step.
Figure 39: How the restart interlock works (1): no one in protective field, machine operates
4 P
ROJECT PLANNING
56
O P E R A T I N G I N S T R U C T I O N S | microScan3 – EtherNet/IP™ 8020200/15ZT/2019-11-14 | SICK