Make sure that dust plugs are plugged on optical fiber connectors equipped with
them during transport of the device. Otherwise, recommissioning is potentially not
possible.
▶ Never touch electronic components.
The following  climatic  conditions  apply  to the storage.  If  required,  appropriate  meas‐
ures must be taken to ensure these climatic conditions (installation of heating/air condi‐
tioning systems etc.):
▶ The storage area must be clean (dust-free, if possible), dry and well-ventilated.
▶ No storage in the open.
▶ The  storage  temperature  must  be  in  the  range  of  −25  °C  to  +55  °C  (−13  °F  to
+131 °F). Shortly it may be +70 °C (+158 °F).
▶ The relative humidity on the storage premises must be in the range of 5 % to 75 %
(no bedewing).
▶ Sudden changes of the temperature or the humidity should be prevented.
▶ Avoid stacking of the devices during transport and storage.
The maximum storage period is 2 years. Electrolytic capacitors produce high leakage
currents when a voltage is applied after a long storage period without applied voltage
and  must  be  reformed.  For  this,  the  operating  voltage  is  applied  via  a  1  kΩ  series
resistor  for  one  hour.  Please  contact  the  SIEB  &  MEYER  service  department  for
details.
3.6 Installation
 
NOTICE
Damage of electrostatically sensitive components due to improper handling
Never touch electronic components.
Consider specific mounting instructions for your device.
Mechanical installation conditions for the system according to DIN EN 61800-2:
Vibrations must remain within the limit values of the IEC 60721-3-3, class 3M1,
standard for fixed equipment.
Frequency [Hz]
Amplitude [mm] Acceleration [m/s²]
2 ≤ 
f
 < 9 0,3 Not applicable
9 ≤ 
f
 < 200 Not applicable 1
Tab. 1: Vibration limits of the system
Vibrations which exceed these limits, or the use on mobile equipment, are considered
as abnormal mechanical conditions.
Operating conditions:
The following requirements are to be considered for the installation and the operation
of the device. Noncompliance with theses requirements is regarded as abnormal oper‐
ating condition:
▶ The device is conceived according to DIN EN 61800-1 / DIN EN 50178 for the dirt
level 2. That means: Ensure to avoid conductive impurities during the operation.
▶ Devices  with  air  cooling  only  can  be  loaded  to  their  maximum  up  to  a  height of
1000 m above MSL (3281 ft above MSL). For an operation in areas higher than