7SR18 Solkor Settings Guide
Unrestricted
Page 6 of 44 © 2016 Siemens Protection Devices Limited
Description Range Default
Remote Phase Current Input 1, 5 1A
Remote Phase CT Ratio Prim ( 6 Character String) 2000
Remote Phase CT Ratio Sec 0.2, 0.21 ... 6.9, 7 1
Remote Earth Current Input 1, 5 1A
Remote Earth CT Ratio Prim ( 6 Character String) 2000
Remote Earth CT Ratio Sec 0.2, 0.21 ... 6.9, 7 1
Gn Phase A Reversal Disabled, Enabled Disabled
Gn Phase B Reversal Disabled, Enabled Disabled
Gn Phase C Reversal Disabled, Enabled Disabled
3 FUNCTION CONFIG
Description Range Default
Gn Prot'n Comms Enabled, Disabled Enabled
Gn Differential Enabled, Disabled Enabled
Gn Intertrip Enabled, Disabled Disabled
Gn Phase Overcurrent Enabled, Disabled Enabled
Gn Voltage Cont O/C Enabled, Disabled Disabled
Gn Cold Load Enabled, Disabled Disabled
Gn Derived E/F Enabled, Disabled Disabled
Gn Measured E/F Enabled, Disabled Enabled
Gn NPS Overcurrent Enabled, Disabled Disabled
Gn Under Current Enabled, Disabled Disabled
Gn Thermal Enabled, Disabled Disabled
Gn Line Check Enabled, Disabled Disabled
Gn CB Fail Enabled, Disabled Disabled
Gn VT Supervision Enabled, Disabled Disabled
Gn CT Supervision Enabled, Disabled Disabled
Gn Broken Conductor Enabled, Disabled Disabled
Gn Trip Cct Supervision Enabled, Disabled Disabled
Gn Close Cct Supervis'n Enabled, Disabled Disabled
Gn Inrush Detector Enabled, Disabled Disabled
Gn CB Counters Enabled, Disabled Disabled
Gn I^2t CB Wear Enabled, Disabled Disabled
4 PROT'N COMMS
4.1 PROTECTION COMMS
Description Range Default
Prot'n Address 1, 2 ... 253, 254 1
Prot'n Comms Alarm Disabled, Enabled Enabled
Prot'n Comms Alarm Delay 1, 2 ... 59, 60 5s
Prot'n Test Mode Off, Loop Test, Line Test Off