7SR18 Solkor Settings Guide
Unrestricted
© 2016 Siemens Protection Devices Limited Page 7 of 44
4.2 INTERTRIP
4.2.1 85
Description Range Default
Gn 85 Enabled, Disabled Disabled
5 DIFFERENTIAL PROT'N
Description Range Default
Local CT Multiplier 0.25, 0.26 ... 2.99, 3 1x
Remote CT Multiplier 0.25, 0.26 ... 2.99, 3 1x
5.1 LINE DIFFERENTIAL
5.1.1 87L-1
Description Range Default
Gn 87L-1 Element Disabled, Enabled Enabled
Gn 87L-1 Initial Setting 0.1, 0.15 ... 2.45, 2.5 0.3xIn
Gn 87L-1 1st Bias Slope 0.1, 0.15, 0.2, 0.25, 0.3, 0.35, 0.4,
0.45, 0.5, 0.55, 0.6, 0.65, 0.7
0.3x
Gn 87L-1 1st Bias Slope Limit 0.5, 0.6 ... 19.9, 20 2xIn
Gn 87L-1 2nd Bias Slope 0.5, 0.55 ... 1.95, 2 1.5x
Gn 87L-1 Delay 0, 0.005 ... 59.9, 60 1s
Gn 87L-1 Offset Disabled, Enabled Enabled
5.1.2 87L-2
Description Range Default
Gn 87L-2 Element Disabled, Enabled Disabled
Gn 87L-2 Initial Setting 0.1, 0.15 ... 2.45, 2.5 0.3xIn
Gn 87L-2 1st Bias Slope 0.1, 0.15, 0.2, 0.25, 0.3, 0.35, 0.4,
0.45, 0.5, 0.55, 0.6, 0.65, 0.7
0.3x
Gn 87L-2 1st Bias Slope Limit 0.5, 0.6 ... 19.9, 20 2xIn
Gn 87L-2 2nd Bias Slope 0.5, 0.55 ... 1.95, 2 1.5x
Gn 87L-2 Delay 0, 0.005 ... 59.9, 60 0s
Gn 87L-2 Offset Disabled, Enabled Enabled
6 DIFFERENTIAL HS
6.1 87HS-1
Description Range Default
Gn 87HS-1 Element Disabled, Enabled Enabled
Gn 87HS-1 Setting 1, 2 ... 29, 30 4xIn
Gn 87HS-1 Delay 0, 0.005 ... 59.9, 60 1s
6.2 87HS-2